Revision of E2749-24 Standard Practice for Measuring the Uniformity of Furnace Exposure on Test Specimens
Rationale
Currently E2749 does not provide information on how far away from the exposed surface the directional flame thermometer (DFT) should be located. This proposed revision provides that information. Currently E2749 does not specify a plate thermometer to be located in the center of the assembly. This proposed revision recommends placing a plate thermometer in the center, to truly capture the uniformity of the furnace temperatures.
Work Item Status
Date Initiated: 06-21-2024
Technical Contact: Kevin Hyland
Item: 004
Ballot: E05 (24-05)
Status: Ballot Item Approved
Item: 003
Ballot: E05 (24-05)
Status: Ballot Item Approved